REPLACEMENT OF SOLENOID VALVE

*** SPECIAL NOTE ***

On RL flakers that are connected to a central refrigeration rack system, a jumper wire must be placed between terminal "Line A" and terminal "Line B ". This jumper will allow the solenoid valve to energize when the operating circuit is energized.

*** SPECIAL NOTE ***

Pump down the ice flaker and evacuate refrigerant from the liquid line. Turn off main power to ice flaker, disconnect wires leads from solenoid valve and remove armored cable. Loosen and remove flare nuts on the solenoid valve and remove the old valve. Install the new valve and tighten the flare nuts.

*** CAUTION ***

ARROW ON SOLENOID VALVE MUST POINT IN THE DIRECTION OF FLOW TOWARDS ICE FLAKER.

*** CAUTION ***

Using a high quality vacuum pump, evacuate to remove any moisture that may have entered the system while the line was open to atmosphere. Re-connect armored cable and solenoid wires. Turn on main power, turn ice flaker switch on and check operation of solenoid valve.

 