REPLACEMENT OF SOLENOID VALVE
Pump down the ice flaker and evacuate refrigerant from the liquid line. Turn off main power to ice flaker, disconnect wires leads from solenoid valve and remove armored cable. Loosen and remove flare nuts on the solenoid valve and remove the old valve. Install the new valve and tighten the flare nuts.
Using a high quality vacuum pump, evacuate to remove any moisture that may have entered the system while the line was open to atmosphere. Re-connect armored cable and solenoid wires. Turn on main power, turn ice flaker switch on and check operation of solenoid valve. |
|